ELMA

Temperature:
-13°F to 149°F (-25°C to 65°C)
Overview

ELMA offers over-signal protection and programmable signal loss protection. By using an internal dip switch, you can program the ELMA to either freeze at the last setting or drive to zero in the event of a signal loss. This means an added level of protection for your pumps as well as your process.

 

Turndown Ratio
10:1
Electric Power Required
120/230 VAC
Maximum Power Consumption
60 watts
Control Range
0 – 100%
Output Signal
4 – 20 mA DC @ 250 ohm Impedance
Dead Band Adjustment
1% to 10%
Response Time
15 seconds
Stroke Length
Fast response time in adjusting stroke length 0-100% in 15 seconds
Ambient Temperature Range
-13°F to 149°F (-25°C to 65°C)
Standard Signal Range
1–5 mA @ 1000 ohm, Impedance 4–20 mA DC @ 250 ohm, Impedance 10–50 mA DC @ 100 ohm, Impedance 1–5 vDC @ greater than 100,000 ohm 3–15 PSI instrument air
Product Options
  • Custom engineered designs
  • High temperature remote head
  • Anti-siphon valve
  • Degassing valve
Accessories

 

Features

  • Provides fast response time in adjusting stroke length 0-100% in 15 seconds
  • Low power consumption – only 60 watts
  • High Resolution Comparator built in to actuator – no separate cabinet required
  • Compact design saves space
  • Easy installation and startup and simplified service
  • Retrofittable to any 680 and 880 pump
  • Modular design for plug-in control options